Monitoring time line supply return (p1213) 
The monitoring time starts when the faults are detected. If the automatic acknowledgments 
are not successful, the monitoring time runs again. If the drive has not successfully restarted 
once the monitoring time has expired (motor magnetization must have been completed: 
r0056.4 = 1), fault F07320 is output. The monitoring is deactivated with p1213 = 0. 
If a fault is pending, fault F07320 will be generated on every restart attempt if the time 
defined in p1213 has expired. If p1210 > 1 and the time in p1213 is set lower than p1212, 
then fault F07320 will also be generated on every restart attempt. The monitoring time must 
be extended if the faults that occur cannot be immediately and successfully acknowledged 
(e.g. when faults are permanently present). 
Commissioning 
1. Activating the function 
–  Automatic restart: Set mode (p1210). 
2. Set starting attempts (p1211). 
3. Set delay times (p1212, p1213). 
4. Check function. 
Overview of important parameters (see SINAMICS S110 List Manual) 
●  r0863 CO/BO: Drive coupling status word/control word 
●  p1210 Automatic restart, mode 
●  p1211 Automatic restart, attempts to start 
●  p1212 Automatic restart, delay time start attempts 
●  p1213 Automatic restart, waiting time increment 