Technical data
  Drive functions 
  7.2 Basic functions 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
189 
p1210  Mode  Meaning 
4  Automatic restart after line 
supply failure, no additional start 
attempts 
If p1210 = 4, an automatic restart will only be 
performed if fault F30003 also occurs on the Power 
Module or there is a HIGH signal at binector input 
p1208[1]. If additional faults are present, then these 
faults are also acknowledged and when successfully 
acknowledged, the starting attempt is continued. 
When the 24 V power supply of the CU fails, this is 
interrupted as a line supply failure. 
6  Restart after any fault with 
additional start attempts 
When p1210 = 6, an automatic restart is carried out 
after any fault or when p1208[0] = 1. If the faults 
occur one after the other, then the number of start 
attempts is defined using p1211. Monitoring over 
time can be set using p1213. 
Starting attempts (p1211) and delay time (p1212) 
p1211 is used to specify the number of starting attempts. The number is internally 
decremented after each successful fault acknowledgment (line supply voltage must be re-
applied). Fault F07320 is signaled if the number of parameterized startup attempts is 
exceeded. 
When p1211 = x, x + 1 starting attempts are made. 
Note 
A start attempt immediately starts when the fault occurs. 
The faults are automatically acknowledged in intervals of half the delay time p1212. 
After successful acknowledgment and voltage recovery, the system is automatically powered 
up again. 
The starting attempt is considered to have been successfully completed once motor 
magnetization (induction motor) is complete (r0056.4 = 1) and one additional second has 
expired. The starting counter is only reset back to the initial value p1211 after this time. 
If additional faults occur between successful acknowledgment and the end of the startup 
attempt, then the startup counter, when it is acknowledged, is also decremented. 










