The pulse number is calculated from the maximum clock frequency of the controller and
the preferred maximum motor speed. The following formula applies:
Pulse number = (max. clock frequency · 60)/max. speed
Example: If the controller has a maximum clock frequency of 100 kHz and the motor
being used is to run at its maximum rated speed of 3000 rpm, the resulting pulse number
will be 2000.
Select one of the following two options for the Signal shape:
Table 7- 21 Signal shapes for the pulse/direction interface
Signal shape p0405[E].5 Graphic
Pulse/direction
positive logic
1
A and B track
positive logic
0
The CU305 automatically links the control signals to the specified inputs/outputs (see the
"Wiring control signals" section).
Setpoint value specification via pulse encoder emulation
For relevant wiring information, refer to the table for "Setpoint value specification:
Encoder signal with TTL level".
As well making the settings in the commissioning wizard (see above), you also need to
set the following values in the drive's expert list:
p0405.0 = 1 (bipolar)
p0405.1 = 1 (TTL)