Technical data
Drive functions
7.1 Servo control
Function Manual
168 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Overview of important parameters (see SINAMICS S110 List Manual)
Adjustable parameters
● p1240 Vdc controller or Vdc monitoring configuration
● p1244 DC link voltage threshold, upper
● p1248 DC link voltage threshold, lower
● p1250 Vdc controller proportional gain
Display parameters
● r0056.14 Vdc_max controller active
● r0056.15 Vdc_min controller active
7.1.15 Travel to fixed stop
Description
This function can be used to move a motor to a fixed stop at a specified torque without a
fault being signaled. When the stop is reached, the specified torque is built up and remains
applied.
The desired torque derating is brought about by scaling the upper/motor-mode torque limit
and the lower/regenerative-mode torque limit.
Application examples
● Screwing parts together with a defined torque.
● Moving to a mechanical reference point.
Signals
When PROFIBUS telegrams 2 to 4 are used, the following are automatically interconnected:
● Control word 2, bit 8
● Status word 2, bit 8
Also with PROFIdrive telegrams 102 and 103:
● Message word, bit 1
● Process data M_red to the scaling of the torque limit