Technical data

Drive functions
7.1 Servo control
Function Manual
152 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Overview of important parameters (see SINAMICS S110 List Manual)
p0341 Motor moment of inertia
p0342 Ratio between the total moment of inertia and that of the motor
p0353 Motor series inductance
p0600 Motor temperature sensor for monitoring
p0640 Current limit
p0642 Encoderless current reduction
p1300 Open-loop/closed-loop control operating mode
p1400.11 Speed control configuration; encoderless operation actual speed value start
value
p1404 Encoderless operation changeover speed
r1407.1 CO/BO: Status word speed controller; encoderless operation active
p1470 Speed controller encoderless operation P-gain
p1472 Speed controller encoderless operation integral-action time
p1498 Load moment of inertia
p1517 Accelerating torque smoothing time constant
p1612 Current setpoint, open-loop control, encoderless
p1755 Motor model without encoder, changeover speed
p1756 Motor model changeover speed hysteresis
7.1.12 Motor data identification
Description
Motor data identification (MotID) provides a means of determining motor data (of third-party
motors, for example). The drive system must have been commissioned for the first time as
basis for using MotID. To do this, either the electrical motor data (motor data sheet) or the
rating plate data must be entered and the calculation of the motor/control parameters
(p0340) must have been completed.
Commissioning involves the following steps:
Enter the motor data or the rating plate data and the encoder data
Complete calculation of the motor and control data as starting value for the MotID (p0340
= 3, if motor data, p0340 = 1, if rating plate data were entered)
Carry out a static measurement (p1910)