Technical data
  Drive functions 
  7.1 Servo control 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
151 
(QFRGHUOHVV
RSHQORRSFRQWUROOHG,I
FORVHGORRSFRQWUROOHG
S RUS 
(QFRGHUHYDOXDWLRQ
3 
FORVHGORRSFRQWUROOHGPRWRUPRGHORSHQORRSFRQWUROOHG
RSHUDWLRQZLWKHQFRGHU
Q
PD[
Q
Q
QPD[
0L[HGRSHUDWLRQ
3 
S!
Q
RSHUDWLRQZLWKHQFRGHU RSHUDWLRQZLWKRXWDQHQFRGHU
Q
PD[
Q
RSHUDWLRQZLWKHQFRGHU RSHUDWLRQZLWKRXWDQHQFRGHU
Q
PD[
S
S
S
S S
S
^
Figure 7-18  Area switchover 
Note 
In closed-loop control operating mode "Speed controller without encoder", a rotor position 
encoder is not required. Since a temperature monitor is not usually connected in this case 
either, this must be parameterized via p0600 = 0 (no sensor). 
Series reactor 
When high-speed special motors are used, or other low leakage induction motors, a series 
reactor may be required to ensure stable operation of the current controller. 
The series reactor can be integrated via p0353. 
Commissioning/optimization 
1. Estimate the motor current p1612 on the basis of the mechanical conditions (I = M/kt). 
2. Set Kn (p1470) and Tn (p1472) above I/f operation (> p1755). The load moment of inertia 
should be set to zero here (p1498 = 0), since this deactivates part of the torque pre-
control. 
3. Determine the load moment of inertia in the speed range above I/f operation (> p1755) by 
setting p1498 via a ramp response (e.g. ramp time 100 ms) and assessing the current 
(r0077) and model speed (r0063). 
Function diagrams (see SINAMICS S110 List Manual)  
●  5050 Kp_n-/Tn_n adaptation 
●  5060 Torque setpoint, control type switchover 
●  5210 Speed controller 










