Technical data
  Drive functions 
  7.1 Servo control 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
131 
●  Offset of the setting values also possible (see "Example: Torque limits with or without 
offset"). 
●  The following torque limits are displayed via parameters: 
–  Lowest of all upper torque limits with and without offset 
–  Highest of all lower torque limits with and without offset 
Fixed and variable torque limit settings 
Table 7- 1  Fixed and variable torque limit settings 
Selection  Torque limitation mode 
Mode  Maximum upper or lower torque limits 
p1400.4 = 0 
Maximum motor or regenerative mode torque 
limits p1400.4 = 1 
Upper torque limit 
(as a positive value) 
p1520  Motor mode torque limit 
(as a positive value) 
p1520 Fixed torque limit 
Lower torque limit 
(as a negative value) 
p1521  Regenerative mode torque limit 
(as a negative value) 
p1521 
Upper torque limit  p1522  Motor mode torque limit  p1522 Source for variable torque 
limit 
Lower torque limit  p1523  Regenerative mode torque limit  p1523 
Upper torque limit  p1528  Motor mode torque limit  p1528 Source for variable scaling 
factor of torque limit 
Lower torque limit  p1529  Regenerative mode torque limit  p1529 
Torque offset for torque 
limit 
Shifts the upper and lower torque 
limits together 
p1532  Shifts the motor and regenerative 
mode torque limits together 
p1532 
Variants of torque limitation 
The following variants are available: 
1. No settings entered: 
The application does not require any additional restrictions to the torque limits. 
2. Fixed limits are required for the torque: 
The fixed upper and lower limits or alternatively the fixed motor and regenerative limits 
can be specified separately by different sources. 
3. Dynamic limits are required for the torque: 
–  The dynamic upper and lower limit or, alternatively, the dynamic motor and 
regenerative limit can be specified separately by different sources. 
–  Parameters are used to select the source of the current limit. 