Technical data

Drive functions
7.1 Servo control
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
131
Offset of the setting values also possible (see "Example: Torque limits with or without
offset").
The following torque limits are displayed via parameters:
Lowest of all upper torque limits with and without offset
Highest of all lower torque limits with and without offset
Fixed and variable torque limit settings
Table 7- 1 Fixed and variable torque limit settings
Selection Torque limitation mode
Mode Maximum upper or lower torque limits
p1400.4 = 0
Maximum motor or regenerative mode torque
limits p1400.4 = 1
Upper torque limit
(as a positive value)
p1520 Motor mode torque limit
(as a positive value)
p1520 Fixed torque limit
Lower torque limit
(as a negative value)
p1521 Regenerative mode torque limit
(as a negative value)
p1521
Upper torque limit p1522 Motor mode torque limit p1522 Source for variable torque
limit
Lower torque limit p1523 Regenerative mode torque limit p1523
Upper torque limit p1528 Motor mode torque limit p1528 Source for variable scaling
factor of torque limit
Lower torque limit p1529 Regenerative mode torque limit p1529
Torque offset for torque
limit
Shifts the upper and lower torque
limits together
p1532 Shifts the motor and regenerative
mode torque limits together
p1532
Variants of torque limitation
The following variants are available:
1. No settings entered:
The application does not require any additional restrictions to the torque limits.
2. Fixed limits are required for the torque:
The fixed upper and lower limits or alternatively the fixed motor and regenerative limits
can be specified separately by different sources.
3. Dynamic limits are required for the torque:
The dynamic upper and lower limit or, alternatively, the dynamic motor and
regenerative limit can be specified separately by different sources.
Parameters are used to select the source of the current limit.