Technical data

Parameterization using the Basic Operator Panel 20
6.1 General information about the BOP20
Function Manual
116 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Information on the displays
Table 6- 1 LED
Display Meaning
top left
2 positions
The active drive object of the BOP is displayed here.
The displays and key operations always refer to this drive object.
RUN Is lit (bright) if the drive is in the RUN state (operation).
RUN is also displayed via bit r0899.2 of the drive.
top right
2 positions
The following is displayed in this field:
More than 6 digits: Characters that are still present but are invisible (e.g. "r2" ––> 2
characters to the right are invisible, "L1" ––> 1 character to the left is invisible)
Designation of BICO inputs (bi, ci)
Designation of BICO outputs (bo, co)
Source object of a BICO interconnection to a drive object different than the active one.
S Is (bright) if at least one parameter was changed and the value was not transferred into the non-
volatile memory.
P Is lit (bright) if, for a parameter, the value only becomes effective after pressing the P key.
C Is light (bright) if at least one parameter was changed and the calculation for consistent data
management has still not been initiated.
Below, 6 digit Displays, e.g. parameters, indices, faults and alarms.
Information on the keys
Table 6- 2 Keys
Key Name Meaning
ON Power up the drive for which the command "ON/OFF1" should come from the BOP.
Binector output r0019.0 is set using this pushbutton.
OFF Powering down the drive for which the commands "ON/OFF1", "OFF2" or "OFF3" should come
from the BOP.
The binector outputs r0019.0, .1 and .2 are simultaneously reset when this key is pressed. After
the key has been released, binector outputs r0019.1 and .2 are again set to a "1" signal.
Functions The significance of this key depends on the current display.
Note:
The effectiveness of this key to acknowledge faults can be defined using the appropriate BiCo
parameterization.
Parameters The significance of this key depends on the current display.
If this key is pressed for 3 s, the "Copy RAM to ROM" function is executed. The "S" displayed on
the BOP disappears.
Raise
Lower
The keys depend on the current display and are used to either raise or lower values.