Technical data

Diagnostics
5.3 Fault and alarm messages
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
111
Triggering messages externally
If the appropriate binector input is interconnected with an input signal, fault 1, 2 or 3 or alarm
1, 2 or 3 can be triggered via an external input signal.
Once an external fault (1 to 3) has been triggered on the Control Unit drive object, this fault
is also present on all associated drive objects. If one of these external faults is triggered on a
different drive object, it is only present on that particular drive object.
BI: p2106 → External fault 1 → F07860(A)
BI: p2107 → External fault 2 → F07861(A)
BI: p2108 → External fault 3 → F07862(A)
BI: p2112 → External alarm 1 → A07850(F)
BI: p2116 → External alarm 2 → A07851(F)
BI: p2117 → External alarm 3 → A07852(F)
Note
An external fault or alarm is triggered by a 1/0 signal.
An external fault and alarm do not usually mean that an internal drive message has been
generated. The cause of an external fault and warning should, therefore, be remedied
outside the drive.
5.3.4 Parameters and function diagrams for faults and alarms
Function diagrams (see SINAMICS S110 List Manual)
1710 Overview diagram – monitoring functions, faults, alarms
8060 Diagnostics - Fault buffer
8065 Diagnostics - Alarm buffer
8070 Diagnostics - Fault/alarm trigger word r2129
8075 Diagnostics - Fault/alarm configuration