Technical data
Diagnostics   
5.3 Fault and alarm messages 
  Function Manual 
110  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Note 
Only those messages which are listed in the indexed parameters can be changed as 
desired. All other message settings retain their factory settings or are reset to the factory 
settings. 
Examples: 
•  In the case of messages listed via p2128[0...19], the message type can be changed. The 
factory setting is set for all other messages. 
•  The fault response of fault F12345 has been changed via p2100[n]. The factory settings 
are to be restored. 
– p2100[n] = 0 
Triggering on messages (example) 
Select message  Trigger signal 
p2128[0] = 1001  BO: r2129.0 
or 
p2128[1] = 1002  BO: r2129.1 
Note 
The value from CO: r2129 can be used as group trigger. 
CO: r2129 = 0 No selected message has been output. 
CO: r2129 > 0 Group trigger. 
At least one selected message has been output. 
The individual binector outputs BO: r2129 should be investigated. 