Operating Manual 
5-23 
5.7.2  ON Key/OFF Key 
ON key: always active in LOCAL when the operator input inhibit is deactivated. 
OFF key: in the factory setting, acts as OFF1 = ramp-down at the deceleration 
ramp (p1121); when n = 0: voltage disconnection (only if a main contactor is 
installed). 
The OFF key is only active in LOCAL mode. 
Settings: Menu: Commissioning / Service – AOP Settings – Control Settings 
Red OFF key acts as: (factory setting: OFF1) 
•  OFF1: Ramp-down on the deceleration ramp (p1121) 
•  OFF2: Immediate pulse block, motor coasts to a standstill 
•  OFF3: Ramp-down on the emergency stop ramp (p1135) 
5.7.3  Switching Between Clockwise and Counter-Clockwise Rotation 
Settings: Menu: Commissioning / Service – AOP Settings – Control Settings 
Switching between CW/CCW (factory setting: no) 
•  Yes: Switching between CW/CCW rotation by means of the CW/CCW key 
possible in LOCAL mode 
•  No: The CW/CCW key has no effect in LOCAL mode 
For safety reasons, the CW/CCW key is disabled in the factory setting (pumps and 
fans must normally only be operated in one direction). 
In the operation status in LOCAL mode, the current direction of rotation is indicated 
by an arrow next to the operating mode. 
NOTE 
You have to make additional settings when switching between CW/CCW rotation. 