Specifications

04/04  Control via the Operator Panel 
SINAMICS G130 - Operator Panel AOP30 
Operating Manual 
5-21 
5.6.4  AOP30 Diagnosis 
Software/Database Version 
You can use this menu to display the firmware and database versions. 
The database version must be compatible with the drive software status (you can 
check this in parameter r0018). 
Battery Status 
In this menu, you can display the battery voltage numerically (in Volts) or as a bar 
display. The battery ensures that the data in the database and the current time are 
retained. 
When the battery voltage is represented as a percentage, a battery voltage of 
≤ 2 V 
is equal to 0%, and a voltage of 
≥ 3 V to 100%. 
The data is secure up to a battery voltage of 2 V. 
•  If the battery voltage is ≤ 2.45 V, the message "Replace battery" is displayed in 
the status bar. 
•  If the battery voltage is ≤ 2.30V, the system displays a popup window with the 
following information "Warning: weak battery". 
•  If the battery voltage is ≤ 2 V, the system displays a popup window with the 
following information: "Warning: battery is empty". 
•  If the time and/or database are not available after the system has been 
switched off for a prolonged period due to the voltage being too low, the loss is 
established by means of a CRC check when the system is switched on again. 
This triggers a message instructing the user to replace the battery and then load 
the database and/or set the time. 
For instructions on changing the battery, see Section 6.1. 
Communication 
In this menu, you can call up information on the communications status between 
the AOP and the drive. 
Key Test 
In this screen, you can check that the keys are functioning properly. Keys that you 
press are represented on a symbolic keyboard on the display. You can press the 
keys in any order you wish. You cannot exit the screen (F5 – "back") until you have 
pressed each key at least once. 
NOTE 
You can also exit the key test screen by pressing any key and keeping it pressed. 
LED Test 
In this screen, you can check that the 4 LEDs are functioning properly. 