Installation Guide

| Load Center Selection & Application Guide
14
Riser Panel Load Centers
a
Riser panel load centers are ideal for high rise applications. The
shifted interior provides room for conductors to pass through
the load center. The tap kits allow the installer to tap off from
those conductors to power the panel.
Features
n
UL Listed for use in 1Ø and 3Ø riser gutter applications.
n
Copper bus standard.
n
Main lug factory standard - convertible to main breaker.
n
Neutrals aligned on left side- keeps way clear for riser cables.
n
Available in 125 and 200 amp models.
n
Invertible for left and right hand applications.
Riser Gutter Tap Kit

The riser gutter tap kit (ECRLK250) allows the installer to
tap off the main conductors, eliminating the need to cut
completely through the conductor. The tap kit accepts 250 -1/0
on the main conductor side and 250-#6 on the tap side.
Riser Gutter
The riser gutter (RAG24) is used to convert any
load center 24” or larger into a riser panel.
Features
n
Single and 3-phase applications
n
Compatible with any single or 3-phase Siemens load center
24" or higher
n
Flush trim included
n
Load center mounting hardware and pass through brush
included (Catalog no. RAG24)
1-phase, 3-wire SN, 120/240 Volts AC
Amp
Rating
No. of
Spaces
No. of
Circuits Catalog Number
Dimensions (inches)
Acceptable
Main Breaker
KitsHeight Width Depth
125 16 32 R1632L1125CU 24 14.25 3.88
MBK100A,
MBK125A
125 24 24 R2424L1125CU 30 14.25 3.88
MBK100A,
MBK125A
125 24 42 R2442L1125CU 30 14.25 3.88
MBK100A,
MBK125A
200 30 42 R3042L1200CU 36 14.25 3.88
MBK150A,
MBK200A
a
The riser panels are single phase only, but can be fed from
1-phase or 3-phase systems running through the gutter
trough area.
ECRLK250 must be ordered in multiples of 3. Each kit con-
tains 3 lugs, however, these are priced per lug not per kit.
ECRLK250 is sold separately
Riser Panel Load Centers
1-Phase, 3-WIre SN, 120/240Volts AC
RAG24Any Load Center
24" or larger
R1632L1125CU
ECRLK250