Data Sheet for Product

4
Siemens
P1 DXR2.T12P
A6V11524146
Building Technologies
2019-07-15
Apparent Power (VA) for Transformer Design
Base Model
Base Load
Max. Load
Triac Output
AC 24V~
0.25 A Each
Max. Load all
Aux. Outputs
AC 24V~
Max. Load
KNX PL-Link
(at 50 mA)
Max. Load
DC 24V+ (2.4
W)
Max. Allowed
Power
Consumption
Including
Connected
Field Devices
DXR2.T12P
6
6 x 6 = 36
12
4
-
58
NOTE:
To calculate the total VA, add the Base Load + number of Triacs + field supplies+ KNX PL-Link.
This cannot exceed the maximum power consumption. See Wiring Guidelines for Field Panels
and Equipment Controllers (125-3002) for more information.
Inputs
Analog Inputs
Resistance Sensor
Temperature Measurement
Voltage Measurement
AI 1000
AI PT1K 375
AI 0 to 10V
AI 2500 Ω
AI PT1K 385
AI 0 to 10V (0 to 100%)
AI 10 KΩ
AI Ni1000
1)
AI 100 KΩ
AI Ni1000 DIN
AI NTC3K
AI NTC10K
1)
AI NTC100K
1)
1)
Configurable default.
Digital Inputs
Contact query voltage
DC 17 V typical
Contact query current
1.5 mA typical, 7 mA initial current
Contact resistance for closed contacts
Less than 100
Contact resistance for open contacts
Greater than 50 kΩ
Differential Pressure Sensor
Connections (nipple diameter)
Diameter 0.20 inch (5.2 mm)
Measuring range
0 to 500 Pa (0 - 2.01 inch WC)
Overload range
0 to 100 kPa (0 - 402 in WC)
Outputs
Analog Outputs
0 to 10V
1.5 mA maximum