Commissioning Instructions
Central Functions
Configuring Group Members and Masters
5
A6V12006922
Restricted
19 | 21
1. Expand the Central function. Modify the Group Number to 1 (It may already be set to 1).
1. With the Group Master selected, the VAV Automation Stations should display in the Group Members
tab.
NOTICE! All Automation Stations used in the Supply Air Temperature Reset calculations must
have an Assigned selection in this tab.
Note: All Central Functions can be grouped hierarchically, which is used for separating Group Member
and Master functions. Multiple Central Functions can be grouped like this to simplify floors, or to split
number of members. One group member can only have 255 objects for supply functions, so it may be
necessary to use two central functions depending on the number of objects.
2. Use Assign Selected or Remove Selected buttons to assign or remove the VAV Automation Stations
from the group.
Once the Terminal application is connected as shown, the Central Function should collect and read by the
data from the VAV box. This will allow the Central Function DXR to communicate with the AHU and
perform Supply Air Temperature Reset correctly.
While online in the Central Function DXR, EvlNumTSuCDmd (CHG DMD QTY) and EvlNumTSuHDmd (HTG
DMD QTY) will show the number of VAV boxes (from the group members) assigned to this DXR.