Data Sheet for Product

5
Siemens Industry, Inc.
A6V10502840
Smart Infrastructure
2020-07-31
Power data
Power supply
Operating voltage AC 24V -15%/+20%
Frequency 50/60 Hz
Internal fuse 4 A irreversible
Transformer with secondary current limitation of max. 10 A
or external secondary current fuse
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN 60898
Apparent power (VA) for transformer design
Base Model
Base load
Max. load Triac
output AC
24V~
0.25 A each
Max. load all
Aux. outputs
AC 24V~
Max. load KNX
PL-Link (at 50
mA)
Max. load
DC 24V+ (2.4
W)
)
Max. Allowed
Power
consumption
including
connected field
devices
DXR2.M18 6 8 x 6 = 48 18 4 6 70
Power for the Triac outputs must be reduced if the maximum load of 18 VA is required for AC
24V field supply on the DXR2.x18.
NOTE:
To calculate the total VA, add the Base Load + the number of Triacs + field supplies+ KNX PL-
Link devices.
This cannot exceed the maximum power consumption. See the
Wiring Guidelines
for more
information.
Inputs
Analog Inputs
Resistance sensor
Temperature measurement
Voltage measurement
AI 1000 AI PT1K 375 (NA)*) AI 0 to 10V
AI 2500 Ω AI PT1K 385 (EU)*) AI 0 to 10V (0 to 100%)
AI 10 KΩ AI (LG-)Ni1000*)
AI 100 KΩ AI Ni1000 DIN*)
AI T1 (PTC)*)
AI NTC10K (Type II)**)
AI NTC100K**)
* A fixed value of 1 Ω is calibrated to correct line resistance.
** Configurable default.
Digital Inputs
Contact voltage Universal input: 18V
Digital input: 21V
Contact current Universal input: 1.2 mA; 7.4 mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ