Data Sheet for Product
5
Siemens Industry, Inc.
A6V10502840
Smart Infrastructure
2020-07-31
Power data
Power supply
Operating voltage AC 24V -15%/+20%
Frequency 50/60 Hz
Internal fuse 4 A irreversible
Transformer with secondary current limitation of max. 10 A
or external secondary current fuse
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN 60898
Apparent power (VA) for transformer design
Base Model
Base load
Max. load Triac
output AC
24V~
0.25 A each
Max. load all
Aux. outputs
AC 24V~
Max. load KNX
PL-Link (at 50
mA)
Max. load
DC 24V+ (2.4
W)
)
Max. Allowed
Power
consumption
including
connected field
devices
DXR2.M18 6 8 x 6 = 48 18 4 6 70
Power for the Triac outputs must be reduced if the maximum load of 18 VA is required for AC
24V field supply on the DXR2.x18.
NOTE:
To calculate the total VA, add the Base Load + the number of Triacs + field supplies+ KNX PL-
Link devices.
This cannot exceed the maximum power consumption. See the
Wiring Guidelines
for more
information.
Inputs
Analog Inputs
Resistance sensor
Temperature measurement
Voltage measurement
AI 1000 Ω AI PT1K 375 (NA)*) AI 0 to 10V
AI 2500 Ω AI PT1K 385 (EU)*) AI 0 to 10V (0 to 100%)
AI 10 KΩ AI (LG-)Ni1000*)
AI 100 KΩ AI Ni1000 DIN*)
AI T1 (PTC)*)
AI NTC10K (Type II)**)
AI NTC100K**)
* A fixed value of 1 Ω is calibrated to correct line resistance.
** Configurable default.
Digital Inputs
Contact voltage Universal input: 18V
Digital input: 21V
Contact current Universal input: 1.2 mA; 7.4 mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ