Commissioning Instructions

Step 7 Default values
11
A6V12035398
Step 7 Default values
To configure a DXR to meet Title 24 requirements, the following features must be
configured as necessary:
Heating coil
Ventilation control
Supply air VAV
Extract air VAV
Heating coil
To support dual maximum VAV control (Dual Max), the following changes must be
made to the heating coil default values.
1) Set the Max.supply air temp.setpoint for heating to be 95°F or lower.
2) Ensure that the Min.supply air temp.setpoint for heating will be lower than the
supply air temperature from the air handler. (eg 50°F).
3) Check the box for Gain to be “Avail. on AS. The Gain will need to be tuned for
each heating coil as the default value may cause instability of the valve position.
Use this formula as a good starting point for the Gain value:
Gain = 0.8 * ( deadband CFM / max heating CFM ) * default gain
Ventilation control
If the area being served by the DXR is required to provide Demand Control Ventilation
(DCV), then the following ventilation control default values MUST be modified.
Step 1: In the DXR, each room operating mode has its own Minimum room air volume
flow setting. (Check “Avail. on AS” as needed.) For DCV, the min air volume flows for
Comfort and Pre-Comfort may typically be the same value. Minimum room air volume
flow should be determined using a minimum ventilation airflow rate of 0.15 CFM/sq ft.
for the area of the room being served by the VAV terminal box. (e.g., 0.15 CFM/sq ft. x
1,000 sq ft = 150 CFM)
Step 2: Set the ventilation control parameters for Comfort and Pre-Comfort
configurations to MinVntDCV - Minimum ventilation and DCV. (a minimum ventilation is
required due to off gassing of VOCs)
Economy and Protection can be set to Off.
Step 3: Set configuration of DCV to use proportional control only. Turn off the integral
control by setting the parameter Integral action time Tn to zero (0).