Commissioning Instructions
DXR Template Feature Selections
A6V12035398
Unrestricted
10
If the fault needs to be monitored using an Event Enrollment Object (monitored as an
alarm), select Activate for each corresponding “Monitor” fault.
Step 6 – Room (HVAC coordination)
To support Dual Max Heat, the following selections are critical:
• VAV terminal units with reheat: you must select VAV temp.cascade heating 11
• FPB terminal units with reheat: you must select FPB temp.cascade heating 11