Application
Point Database
74
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
103
RM UNIT ST21
BAPerip
heralDev
ice
414
ROpUn 1
Room operator unit 1
Operat.
--
1:Operat.
2:DevStopd
3:DevNAsgn
4:DevMisng
5:CnfngDev
6:Unused
7:CnfError
8:Searchng
--
--
104
OP MODE EFF
MCalcVa
l
521
PrOpMod
Present operating mode
Protect
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
105
VAV MODE
MPrcVal
592
VavSuDev
Mod
Supply air VAV device
mode
Off
--
1:Off
2:CtrlMod
3:MxAiVlFl
4:MnAiVlFl
5:SmCtAFlS
--
--
106
1VAV CHGVR
MPrcVal
593
VavSuChovr
Cnd1
Supply air VAV
changeover condition 1
Neither
--
1:Neither
2:Heating
3:Cooling
4:Neutral
--
--
107
2VAV CHGVR
MPrcVal
594
VavSuChovr
Cnd2
Supply air VAV
changeover condition 2
Neither
--
1:Neither
2:Heating
3:Cooling
4:Neutral
--
--
108
SU AIR1DMD
MCalcVa
l
595
VavSuAirD
md1
Supply air VAV air
demand 1 f.plant mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:Cooldown
8:RmLTProt
9:CdOvrFPr
10:FreeCool
11:NghtCool
12:Vent
13:EqTmpPro
14:ArVlFlwO
15:SmkCPoPr
16:SmkCNgPr
17:Purge
--
--