Application
Point Database
71
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
50
AIR VEL2EF
ACalcVal
696
VavSuAirVE
ff2
Supply air VAV effective
air velocity 2
--
ft/m
(m/s)
--
--
--
51
AIR VOL2SP 1
APrcVal
697
VavSuSpAir
Fl2
Supply air VAV setpoint
f.air vol.flow 2
--
ft3/m
(lps)
--
--
--
52
FLO REL2SP
ACalcVal
698
VavSuSpAfl
Rel2
Supply air VAV
setp.f.rel.air vol.flow 2
--
PCT
--
--
--
53
SU AIR2VOL 1
ACalcVal
699
VavSuAirFl2
Supply air VAV air
volume flow 2
--
ft3/m
(lps)
--
--
--
54
SU AIR2FLO
ACalcVal
700
VavSuAirFl
Rel2
Supply air VAV rel.air
volume flow 2
--
PCT
--
--
--
55
AIR FL 2DV
ACalcVal
701
VavSuAirFl
Dvn2
Supply air VAV air
volume flow deviat.2
--
PCT
--
--
--
56
AIRVOL TOT
ACalcVal
702
VavSuAirFl
Tot
Supply air VAV total air
volume flow
--
ft3/m
(lps)
--
--
--
57
VAV CLG REQ
ACalcVal
703
VavSuCReq
Supply air VAV cooling
request
--
PCT
--
--
--
58
VAV HTG REQ
ACalcVal
704
VavSuHReq
Supply air VAV heating
request
--
PCT
--
--
--
59
VAV VENT REQ
ACalcVal
705
VavSuVntR
eq
Supply air VAV
ventilation request
--
PCT
--
--
--
60
VAV VNT
FLOW
ACalcVal
706
VavSuAflPv
dVnt
Supply air VAV provided
air flow f.vent.
--
ft3/m
(lps)
--
--
--
61
CLG FLOW
MAX
ACnfVal
731
VavSuAirFl
MaxC
Supply air VAV max.air
vol.flow f.cool.
1000
(500)
ft3/m
(lps)
--
--
--
62
CLG FLOW
MIN
ACnfVal
732
VavSuAirFl
MinC
Supply air VAV min.air
vol.flow f.cool.
0
ft3/m
(lps)
--
--
--
63
HTG FLOW
MAX
ACnfVal
733
VavSuAirFl
MaxH
Supply air VAV max.air
vol.flow f.heat.
800
(400)
ft3/m
(lps)
--
--
--
64
HTG FLOW
MIN
ACnfVal
734
VavSuAirFl
MinH
Supply air VAV min.air
vol.flow f.heat.
100
(50)
ft3/m
(lps)
--
--
--
65
VENT FLO
MAX
ACnfVal
735
VavSuAflM
axVnt
Supply air VAV max.air
vol.flow f.vent.
500
(250)
ft3/m
(lps)
--
--
--
66
VENT FLO MIN
ACnfVal
736
VavSuAflMi
nVnt
Supply air VAV min.air
vol.flow f.vent.
0
ft3/m
(lps)
--
--
--
67
VAV CLG DMD
ACalcVal
737
VavSuCDm
d
Supply air VAV cooling
demand
--
PCT
--
--
--
68
VAV HTG DMD
ACalcVal
738
VavSuHDm
d
Supply air VAV heating
demand
--
PCT
--
--
--
69
VAV VENT
DMD
ACalcVal
739
VavSuVntD
md
Supply air VAV
ventilation demand
--
PCT
--
--
--
70
SUP HTG SP
APrcVal
749
HclSpTSuH
Heating coil sply.air
temp.setp.f.heat
--
DEG F
(DEG C)
--
--
--
71
CMF BTN
BPrcVal
0
CmfBtn
Comfort button
Inactive
--
--
Active
Inactive
72
RAPID VENT
BPrcVal
2
RpdVnt
Rapid ventilation
Off
--
--
On
Off
73
NGT CLG REQ
BCalcVal
3
NgtCReq
Night cooling request
Inactive
--
--
Active
Inactive
74
COOL DN REQ
BCalcVal
4
CoolDwnRe
q
Cool down request
Inactive
--
--
Active
Inactive
75
WARM UP REQ
BCalcVal
5
WarmUpRe
q
Warm-up request
Inactive
--
--
Active
Inactive