Application

Room Functions
Room Operator Unit
37
Application Note
A6V11692042
2019-04-01
from all room segments combined into a Room configuration.
Navigation: , Key 1:
Display outside air quality: The air quality of the outside is displayed.
Navigation: , Key 1:
Note: This setting is only meaningful if a value for the air quality of the outside is
available.
Display room & outside air quality: The air quality of the room and of the outside
are displayed. Toggling between the values is enabled.
Navigation: , Key 1:
Note: This setting is only meaningful if a value for the air quality of the outside is
available.
Room unit, air quality display
Room unit, air quality display defines how the air quality is displayed.
Numeric, in ppm: The air quality is displayed as numeric value in ppm.
Symbolic: The air quality is displayed with the symbols --+, -++, and +++.
Textual: The air quality is displayed as Poor, Ok, or Good.
Room unit, display heating/cooling status
Room unit, display heating/cooling status enables or disables the display of the
plant state.
Yes: Icons indicate if the plant is heating or cooling.
No: The plant state is not displayed.
Room unit, room temp. setpoint display
Room unit, room temp. setpoint display defines how the shift in the temperature
setpoint is displayed.
Absolute temperature setpoint: The room temperature setpoint is displayed as
absolute temperature value.
Relative setpoint shift: The value by which the temperature setpoint is changed is
displayed.
Enable operation: room temperature setpoint
Enable operation: room temperature setpoint defines if the temperature setpoint or
the shift of the temperature setpoint is displayed and if the user can change either.
Yes: The temperature setpoint or the shift of the temperature setpoint is displayed
and the user can change it. This setting is only meaningful if the room temperature
sensor is enabled.
Navigation:
No: Neither the temperature setpoint nor the shift for the temperature setpoint is
displayed and they cannot be changed.