Application

Room Functions
Room Operating Mode Determination
32
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure Building Products
2019-04-01
Setting TiCmfBtn to 0 will disable the Comfort button. If the Presence button is
configured, setting TiCmfBtn to 0 only disables the timer; in this case, Comfort
mode remains in effect until the next schedule change unless the Presence button
is pressed again.
Outputs:
ROpModDtr outputs the following:
ROpMod - The room operating mode is distributed to HVAC, lighting and
shading AFs.
PrOpMod - The present operating mode can be configured for display on the
room operator unit.
ManOpCnd - Manual operation condition can be configured / set to Locked
(default = Unlocked). When Locked, manual attempts to adjust the setpoint are
blocked during the operating mode(s) defined in the parameter for Manual
operation lock configuration (ManOpLockCnf). The default for ManOpLockCnf
= Protection & Economy this means that manual attempts to increase comfort
are blocked during Economy and Protection modes.
Note: Setting ManOpCnd to Locked does not lock out manual changes to
lighting or shading; it only locks out HVAC changes.
CmfCndTrg / EefCndTrg (see Configuration)
Comfort condition trigger (CmfCndTrg) specifies transition of room mode
from less comfort to more comfort.
Energy efficiency condition trigger (EefCndTrg) specifies transition of room
mode away from comfort.
Central triggering
Manual setpoint adjustment & EefCndTrg
The default configuration will reset a user-entered setpoint adjustment when the
room mode changes. To eliminate this reset, do the following:
- Set Comfort/Pre-Comfort to Economy (CmfPcfToEco) to "None"
- Set Comfort to Pre-Comfort (CmfToPcf) to "None"
These parameters are in the AF, Room operating mode determination
ROpModDtr. They are not BACnet objects, so ABT Site or SSA is required to
access them.