Application

14022 Point Database
75
Siemens Industry, Inc.
A6V11692055
Smart Infrastructure Building Products
2019-04-01
14269 Point Database
The table shows US engineering units and values, and also CA engineering units
and values. CA values are shown in parentheses ( ).
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Defaul
t
Value
Units
Enumeration
On
Text
Off
Text
1
ROOM TEMP 4
AI
57
TR
Room temperature
--
DEG F
(DEG C)
--
--
--
2
SPLY TEMP 4
AI
128
TSu
Supply air temperature
--
DEG F
(DEG C)
--
--
--
3
SU DIFF 1P 3
AI
186
VavSuDiffP
1
Supply air VAV
differential pressure 1
--
in H2O
(Pa)
--
--
--
4
SU DIFF 2P 4
AI
191
VavSuDiffP
2
Supply air VAV
differential pressure 2
--
in H2O
(Pa)
--
--
--
5
COND STA 1
BI
20
CdnMon
Condensation monitor
Off
--
--
On
Off
6
RAD V POS 2
AO
120
RadVlvPos
1
Radiator valve position 1
--
PCT
--
--
--
7
PANL C POS10
AO
164
RcgVlvPosC
1
Radiant ceiling valve
pos.for cooling 1
--
PCT
--
--
--
8
1DMPR POS 5
AO
247
VavSuPos1
Supply air VAV position 1
--
PCT
--
--
--
9
2DMPR POS 5
AO
251
VavSuPos2
Supply air VAV position 2
--
PCT
--
--
--
10
HTG EL 1ST 2
BO
100
HclEl1StPo
s
Heating coil electric
pos.first stage
Off
--
--
On
Off
11
HTG EL 2ST 2
BO
102
HclEl2StPo
s
Heating coil electric
pos.second stage
Off
--
--
On
Off
12
APPLICATION
ACnfVal
4
AppNr
Application number
14269
--
--
--
--
13
CMF CLG
STPT
APrcVal
14
SpCCmf
Cooling setpoint for
comfort
75
(24)
DEG F
(DEG C)
--
--
--
14
STBY C DELTA
ACnfVal
15
DSpCPcf
Delta cooling setpoint for
pre-comfort
2
(1)
DEG F
(DEG K)
--
--
--
15
CLG STPT EFF
APrcVal
16
PrSpC
Present cooling setpoint
--
DEG F
(DEG C)
--
--
--
16
PROT
CLGSTPT
ACnfVal
17
SpCPrt
Cooling setpoint for
protection
104
(40)
DEG F
(DEG C)
--
--
--
17
ECO CLG STPT
ACnfVal
18
SpCEco
Cooling setpoint for
economy
85
(30)
DEG F
(DEG C)
--
--
--
18
STBY C SPEFF
ACalcVal
19
PrSpCPcf
Present cooling setpoint
for pre-comfort
--
DEG F
(DEG C)
--
--
--
19
CMF C SP EFF
ACalcVal
20
PrSpCCmf
Present cooling setpoint
for comfort
--
DEG F
(DEG C)
--
--
--
20
ECO C SP EFF
ACalcVal
21
PrSpCEco
Present cooling setpoint
for economy
--
DEG F
(DEG C)
--
--
--
21
PROT C SPEFF
ACalcVal
22
PrSpCPrt
Present cooling setpoint
for protection
--
DEG F
(DEG C)
--
--
--
22
CMF HTG
STPT
APrcVal
32
SpHCmf
Heating setpoint for
comfort
70
(21)
DEG F
(DEG C)
--
--
--
23
PROT HTG SP
ACnfVal
33
SpHPrt
Heating setpoint for
protection
45
(7)
DEG F
(DEG C)
--
--
--