Application
Room Segment Functions
Device Control Functions HVAC
59
Siemens Industry, Inc.
Application Note
A6V11692055
Smart Infrastructure – Building Products
2019-04-01
Airflow Sequencing and Airflow Limits
The VAV airflow controller adjusts airflow to accomplish cooling and ventilation,
and to support heating from the heating coil.
Each function has an operating range selected by the engineer to satisfy particular
physical objectives. This design separates minimum cooling flow and minimum
heating flow from the flow rate needed for ventilation.
The ventilation rate can be constant, vary with room occupancy mode, or vary
according to IAQ measurements. These factors have no effect on the flow rate
needed for the heating and cooling processes and devices (airflow through heating
coil, airflow needed for ceiling louver, etc.).
The following table provides suggestions for setting parameters affecting airflow
when the control system is in the cooling, ventilation and heating part of the control
sequence. See
Operating Diagrams
in
Section 1
for a pictorial of the relationship of
these parameters.
Object
Description
Most common use
VavSuAirFlMaxC
Supply air VAV maximum air volume
flow for cooling
The highest flow rate for the terminal or space that corresponds
to cooling load.
VavSuAirFlMinC
Supply air VAV minimum air volume
flow for cooling
The lowest flow rate for the terminal or space that allows cooling
to work properly.
VavSuAirFlMaxH
Supply air VAV maximum air volume
flow for heating
The highest flow rate for the terminal or space and should be half
of the cooling max to comply with standard codes.
VavSuAirFlMinH
Supply air VAV minimum air volume
flow for heating
The lowest flow rate for the terminal or space that allows heating
to work properly.
VavSuAflMaxVnt
Supply air VAV maximum air volume
flow for ventilation
The highest flow rate that the DCV loop can request (can be equal
to max cooling).
VavSuAflMinVnt
Supply air VAV minimum air volume
flow for ventilation
The lowest flow rate for ventilation to work properly.
AirFlMinRCmf
Minimum room air volume flow for
comfort
The primary airflow rate (not OA ventilation) required when the
space is occupied.
AirFlMinRPcf
Minimum room air volume flow for pre-
comfort
The primary airflow rate required when the space is in standby
mode.
AirFlMinREco
Minimum room air volume flow for
economy
The primary airflow rate required when the space is unoccupied.
In many spaces this should be
Fan coasting feature
Note
The fan coasting feature applies to duct 1 and duct 2 separately: there is a fan
coasting object for each duct (FanSuCstVal1, FanSuCstVal2).
The fan coasting feature (FanSuCstVal) prevents premature closing of the room
supply damper while the AHU fan is coasting down. This might occur during a
switch between operating modes (for example, switching from Comfort to
Economy).
The fan coasting feature is active when:
⚫ The room supply air damper is the only damper that is open – all other VAV
supply air dampers are closed.
⚫ The AHU supply fan has been turned off and is coasting down.