Application

Point Database
87
Siemens Industry, Inc.
A6V11692053
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
50
SU AIR1VOL 1
ACalcVal
693
VavSuAirFl1
Supply air VAV air
volume flow 1
--
ft3/m
(lps)
--
--
--
51
SU AIR1FLO
ACalcVal
694
VavSuAirFlRel1
Supply air VAV rel.air
volume flow 1
--
PCT
--
--
--
52
AIR FL 1DV
ACalcVal
695
VavSuAirFlDvn1
Supply air VAV air
volume flow deviat.1
--
PCT
--
--
--
53
AIR VEL2EF
ACalcVal
696
VavSuAirVEff2
Supply air VAV effective
air velocity 2
--
ft/m
(m/s)
--
--
--
54
AIR VOL2SP 1
APrcVal
697
VavSuSpAirFl2
Supply air VAV setpoint
f.air vol.flow 2
--
ft3/m
(lps)
--
--
--
55
FLO REL2SP
ACalcVal
698
VavSuSpAflRel2
Supply air VAV
setp.f.rel.air vol.flow 2
--
PCT
--
--
--
56
SU AIR2VOL 1
ACalcVal
699
VavSuAirFl2
Supply air VAV air
volume flow 2
--
ft3/m
(lps)
--
--
--
57
SU AIR2FLO
ACalcVal
700
VavSuAirFlRel2
Supply air VAV rel.air
volume flow 2
--
PCT
--
--
--
58
AIR FL 2DV
ACalcVal
701
VavSuAirFlDvn2
Supply air VAV air
volume flow deviat.2
--
PCT
--
--
--
59
AIRVOL TOT
ACalcVal
702
VavSuAirFlTot
Supply air VAV total air
volume flow
--
ft3/m
(lps)
--
--
--
60
VAV CLG REQ
ACalcVal
703
VavSuCReq
Supply air VAV cooling
request
--
PCT
--
--
--
61
VAV HTG REQ
ACalcVal
704
VavSuHReq
Supply air VAV heating
request
--
PCT
--
--
--
62
VAV VENT REQ
ACalcVal
705
VavSuVntReq
Supply air VAV
ventilation request
--
PCT
--
--
--
63
VAV VNT
FLOW
ACalcVal
706
VavSuAflPvdVnt
Supply air VAV provided
air flow f.vent.
--
ft3/m
(lps)
--
--
--
64
CLG FLOW
MAX
ACnfVal
731
VavSuAirFlMaxC
Supply air VAV max.air
vol.flow f.cool.
1000
(500)
ft3/m
(lps)
--
--
--
65
CLG FLOW
MIN
ACnfVal
732
VavSuAirFlMinC
Supply air VAV min.air
vol.flow f.cool.
0
ft3/m
(lps)
--
--
--
66
HTG FLOW
MAX
ACnfVal
733
VavSuAirFlMaxH
Supply air VAV max.air
vol.flow f.heat.
800
(400)
ft3/m
(lps)
--
--
--
67
HTG FLOW
MIN
ACnfVal
734
VavSuAirFlMinH
Supply air VAV min.air
vol.flow f.heat.
100
(50)
ft3/m
(lps)
--
--
--
68
VENT FLO
MAX
ACnfVal
735
VavSuAflMaxVnt
Supply air VAV max.air
vol.flow f.vent.
500
(250)
ft3/m
(lps)
--
--
--
69
VENT FLO MIN
ACnfVal
736
VavSuAflMinVnt
Supply air VAV min.air
vol.flow f.vent.
0
ft3/m
(lps)
--
--
--
70
VAV CLG DMD
ACalcVal
737
VavSuCDmd
Supply air VAV cooling
demand
--
PCT
--
--
--
71
VAV HTG DMD
ACalcVal
738
VavSuHDmd
Supply air VAV heating
demand
--
PCT
--
--
--
72
VAV VENT
DMD
ACalcVal
739
VavSuVntDmd
Supply air VAV
ventilation demand
--
PCT
--
--
--
73
CMF BTN
BPrcVal
0
CmfBtn
Comfort button
Inactive
--
--
Active
Inactive
74
RAPID VENT
BPrcVal
2
RpdVnt
Rapid ventilation
Off
--
--
On
Off
75
NGT CLG REQ
BCalcVal
3
NgtCReq
Night cooling request
Inactive
--
--
Active
Inactive