Data Sheet for Product

8
A6V10502838
2021-07-19
KNX/PL-Link Network and Power Wriring.*
Cable configuration 1 or 2 twisted pair
- Pair 1 red/black
- Pair 2 yellow/white
Gauge 20 AWG (solid copper)
Twists per foot 4 Minimum
Capacitance 30 pF/foot or less
Shields 100% foil with drain wire
UL type 300Vrms, CMP (75 °C or higher)
CSA type 300Vrms, FT6 (75 °C or higher)
* Alternative 18 AWG STP CMP (Belden 6320FE 8771000)
Conformity
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Ambient Conditions and Protection classification
Climatic ambient conditions
Transport and storage
Operation
Temperature -25 to 70°C (-13 to 158°F)
Air humidity 5 to 95% rh.
Temperature -5 to 45°C (23 to 113°F)/
-5 to 50°C (23 to 122°F)
Air humidity 5 to 95% rh.