Application

Point Database
70
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
24
CMF H SP EFF
ACalcVal
36
PrSpHCmf
Present heating setpoint
for comfort
--
DEG F
(DEG C)
--
--
--
25
STBY H SPEFF
ACalcVal
37
PrSpHPcf
Present heating setpoint
for pre-comfort
--
DEG F
(DEG C)
--
--
--
26
HTG STPT EFF
APrcVal
38
PrSpH
Present heating setpoint
--
DEG F
(DEG C)
--
--
--
27
ECO H SP EFF
ACalcVal
39
PrSpHEco
Present heating setpoint
for economy
--
DEG F
(DEG C)
--
--
--
28
PROT H SPEFF
ACalcVal
40
PrSpHPrt
Present heating setpoint
for protection
--
DEG F
(DEG C)
--
--
--
29
RM TEMP
STPT
APrcVal
41
SpTR
Room temperature
setpoint
--
DEG F
(DEG C)
--
--
--
30
RM TEMP
SHFT
APrcVal
42
SpTRShft
Room temperature
setpoint shift
0
DEG F
(DEG K)
--
--
--
31
ECO DCV STPT
ACnfVal
45
SpAQualRE
co
Setpoint room air quality
for economy
1500
ppm
--
--
--
32
PROT DCV SP
ACnfVal
46
SpAQualRP
rt
Setpoint room air quality
for protection
2000
ppm
--
--
--
33
STBY DCV SP
ACnfVal
47
SpAQualRP
cf
Setp.room air quality for
pre-comfort
1200
ppm
--
--
--
34
VENT SP EFF
APrcVal
48
PrSpVnt
Present ventilation
setpoint
--
ppm
--
--
--
35
CMF IAQ STPT
ACnfVal
49
SpAQualRC
mf
Setpoint room air quality
for comfort
1000
ppm
--
--
--
36
RM DCV EVAL
ACalcVal
50
RAQual
Room air quality
--
ppm
--
--
--
37
RM TEMP
EVAL
ACalcVal
51
RTemp
Room temperature
--
DEG F
(DEG C)
--
--
--
38
OA TEMP 1
APrcVal
52
TOa
Outside air temperature
--
DEG F
(DEG C)
--
--
--
39
OA HUM 1
APrcVal
53
HuRelOa
Relative outside humidity
--
rh
--
--
--
40
RM HUM EVAL
ACalcVal
54
RHuRel
Relative humidity for
room
--
rh
--
--
--
41
REHTG POS
ACalcVal
57
ReHclPos
Reheating coil position
--
PCT
--
--
--
42
HTG COIL MIN
ACalcVal
275
HclHReqMi
n
Heating coil heating
request minimum
--
PCT
--
--
--
43
HTG COIL REQ
ACalcVal
276
HclHReq
Heating coil heating
request
--
PCT
--
--
--
44
AIR VEL1EF
ACalcVal
690
VavSuAirVE
ff1
Supply air VAV effective
air velocity 1
--
ft/m
(m/s)
--
--
--
45
AIR VOL1SP 1
APrcVal
691
VavSuSpAir
Fl1
Supply air VAV setpoint
f.air vol.flow 1
--
ft3/m
(lps)
--
--
--
46
FLO REL1SP
ACalcVal
692
VavSuSpAfl
Rel1
Supply air VAV
setp.f.rel.air vol.flow 1
--
PCT
--
--
--
47
SU AIR1VOL 1
ACalcVal
693
VavSuAirFl1
Supply air VAV air
volume flow 1
--
ft3/m
(lps)
--
--
--
48
SU AIR1FLO
ACalcVal
694
VavSuAirFl
Rel1
Supply air VAV rel.air
volume flow 1
--
PCT
--
--
--
49
AIR FL 1DV
ACalcVal
695
VavSuAirFl
Dvn1
Supply air VAV air
volume flow deviat.1
--
PCT
--
--
--