Commissioning Instructions
Supply Air Temperature Reset and Zone Demand
Poor Indicators of Zone Load
3
6 | 21
Restricted
A6V12006922
3 Supply Air Temperature Reset and Zone Demand
Keeping the Supply Air Temperature (SAT) at a constant temperature can be effective in certain situations
but can also lead to wasted energy and increased costs in other scenarios. A common practice, even
required by some guidelines and standards, is to reset the SAT regularly to a temperature that can reduce
the amount of heating and cooling to the air, as well as reducing fan energy. By implementing SAT Reset,
the control system has more flexibility to efficiently satisfy the zone, regardless of the load required.
By using central functions, it is possible to collect data from each VAV box and use it to automatically reset
supply air temperature if necessary. ASHRAE recommends choosing from available strategies that reset the
supply air temperature setpoint based on building loads or outside air temperature.
This document focuses on the simple and efficient demand signal method to achieve supply air
temperature reset.
3.1 Poor Indicators of Zone Load
1. Outside air temperature does not consider internal loads into the reset. If the temperature is reset
when external loads are low but internal loads are high, the space could become over-heated.
2. Return air temperature provides overall average but does not consider individual zones that may have
internal loads. Some zones may be well above the average, while others may be well below.
3. Zone temperature (room temperature) does not consider building inhabitant factors. If a zone is
chosen to represent a hot or cold section of the building, that could change depending on the load. For
example, if a zone is chosen to represent the coldest area, people in the zone may add things like local
space heaters for comfort, thus making the zone reading much higher than normal.
3.2 Good Indicators of Zone Load
The cooling or heating demand signal (PID controller) from an air terminal provides a good demand
indicator for supply air temperature. When an air terminal is in cooling and meets air-flow conditions but
fails to meet zone comfort conditions in the space served, it requires the colder supply air. The same is true
in reverse for heating. Therefore, using the output of the cooling or heating PID controller for an air
terminal provides a good demand indicator for supply air temperature.
In every Supply Air VAV (VavSuXX) application function, BACnet objects send the Heating and Cooling
demand out to be read by Central Functions or the AHU. These points send a heating and cooling demand
signal (from 0-100%) that the Supply Air Central Function collects for every terminal.
The central function averages the highest 10 values to determine how to increase or decrease the supply
air temperature setpoint. By evaluating the number of zones that call for cooling or heating as well as the
average demand of the zones, the central function can continuously optimize the supply air to be at an
appropriate temperature.
When the terminal DXRs are assigned to the central function group the calculations for Supply Air Setpoint
will occur, and varying setpoints will be sent to the AHU as loads change.
Group Master Object
The Group Master object in the Central Function application for supply air coordination collects data from
supply air Group Members to support supply air temperature reset.