Application
14022 Point Database
79
Siemens Industry, Inc.
Application Note
A6V11692055
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Defaul
t
Value
Units
Enumeration
On
Text
Off
Text
95
PLNK STATUS
CmnEvt
4
PlnkBusSta
KNX PL-Link bus state
Norma
l
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
96
RM STATUS
CmnEvt
8
RSta
Room state
Norma
l
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
97
SEGM STATUS
CmnEvt
9
RSegmSta
Room segment state
Norma
l
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
98
RM OP MODE
MPrcVal
13
ROpMod
Room operating mode
Protec
t
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
99
GREEN LEAF
MPrcVal
15
REei
Energy efficiency
indication room
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
100
RM LGT
GRNLF
MCalcVa
l
16
RLgtEei
Room energy efficiency
ind.lighting
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
101
RM SHD
GRNLF
MCalcVa
l
17
RShdEei
Room energy efficiency
ind.shading
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
102
RMHVAC
GRNLF
MCalcVa
l
20
RHvacEei
Room energy efficiency
indication HVAC
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
103
H.C STATE
MCalcVa
l
21
HCSta
Heating/cooling state
Neithe
r
--
1:Neither
2:Heating
3:Cooling
--
--
104
NEXT OP
MODE
MPrcVal
22
NxROpMod
Next room operating
mode
Protec
t
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--