6. Expand the Central function. Modify the Group Number to 1. (It may
already be set to 1)
7. With the Group Master selected, the VAV Automation Stations should be
displayed in the Group Members tab. All Automation Stations used in the
Duct Pressure Reset calculations must have an Assigned selection in this
tab.
All Central Functions can be grouped hierarchically, which is used for separating
Group Member and Master functions. Multiple Central Functions can be grouped like
this to simplify floors, or to split number of members. One group member can only have
255 objects for supply functions, so it may be necessary to use two central functions
depending on the number of objects.