Assortment / System Description

Rooms and room segments
7
A6V10866237_en--_b_08 21 | 275
The given room function is once again enabled when dividing up a large room to
various smaller rooms and connected to the associated room segment
functions.
The system ensures that there is only one active room function per room and
supports the switching of room segments with the same application types. The
following combinations are examples of possible multisegment applications for
one DXR2 with one fan coil application type:
Combination DXR2 DXR2
1 Fan coil application Fan coil application
2 Fan coil application with chilled ceiling and/or
radiator application
Fan coil application with chilled
ceiling and/or radiator
application
3 Fan coil application with chilled ceiling and/or
radiator application
Fan coil application
4 Fan coil application with chilled ceiling and/or
radiator application
Chilled ceiling and/or radiator
application
5 Chilled ceiling and/or radiator application Chilled ceiling and/or radiator
application
The following combinations are examples of possible multisegment applications
for one DXR2 with one VAV application type:
Combination DXR2 DXR2
1 VAV application (supply and extract air) VAV application (supply and
extract air)
2 VAV application (supply air and/or extract air)
with chilled ceiling and/or radiator application
VAV application (supply air
and/or extract air) with chilled
ceiling and/or radiator
application
3 VAV application (supply air and/or extract air)
with chilled ceiling and/or radiator application
VAV application (supply and
extract air)
4 VAV application (supply air and/or extract air)
with chilled ceiling and/or radiator application
Chilled ceiling and/or radiator
application
5 Chilled ceiling and/or radiator application Chilled ceiling and/or radiator
application
Combinations of one DXR2 with fan coil application and one DXR2 with VAV
application cannot be configured.