Data Sheet for Product

3
Siemens Industry, Inc.
A6V10502834
2020-07-31
Blinds one or two separate zones
Manual control: Up, Down, Predefined positions
Occupancy control and Vacancy control
Glare Protection
Energy efficiency functions including solar radiation optimization
Slat angle
Scene control
Pre-loaded Application Options
Fan coil unit
Single, multiple or variable speed fan control.
Outside air damper control with economizer.
Ventilation Control or Demand Control Ventilation (DCV) with separate outside air damper
(OAD) setpoints for each operational mode.
Supply (discharge) air temperature control for modulation heating or cooling coils.
Dehumidification control.
Terminal coils: heating (hot water or electric), cooling (chilled water or DX) and
heating/cooling coil (2-pipe or 4-pipe).
Radiant ceiling including Chilled beams and Radiator control.
Heat pump
Heat Pump compressors: Single, multiple or variable speed.
Air-to-air, water loop or ground water configurations.
Single, multiple or variable speed fan control.
Outside air damper control with economizer.
Dehumidification control.
Ventilation Control or Demand Control Ventilation (DCV) with separate outside air damper
(OAD) setpoints for each operational mode.
Terminal heating coil (hot water or electric) or hot gas coil.
Radiant ceiling including Chilled beams and Radiator control.
Greenleaf energy efficiency determination and display.
Configurable plant operating modes (heating, cooling, warm up, cool down, flush/purge, and
so on).
The selected application and its parameters as well as input and output configuration determine
the room automation station's functionality.
A detailed description of functionality is available in the ABT (Automation Building Tool) online
help.
Communication
BACnet MS/TP
USB connection for service and commissioning, firmware download, and LAN access.
The following functions are available with the KNX PL-Link bus:
Communication with room operator units, switches, sensors, actuators, and luminaires.
Plug-and-play connection of Siemens field devices with KNX PL-Link.