Application
Point Database
97
Siemens Industry, Inc.
Application Note
A6V11692053
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Instan
ce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
99
PLANT
OPMODE
MPrcVal
27
PltOpMod
Plant operating mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:CoolDown
8:RmLTProt
9:NUsed1
10:FreeCool
11:NghtCool
12:Vent
13:NUsed2
14:AVlFlOf
15:SmCtPoPr
16:SmCtNgPr
17:Purge
--
--
100
DCV IND EVAL
MCalcVal
28
RAQualInd
Room air quality
indication
Undef
--
1:Undef
2:Poor
3:Okay
4:Good
--
--
101
HC DEMAND
MCalcVal
35
HCDmd
Heating/cooling
demand
Neither
--
1:Neither
2:Heating
3:Cooling
--
--
102
RAD DEV
MODE
MPrcVal
37
RadDevMod
Radiator device mode
Off
--
1:Off
2:CtrlMode
3:FullOpen
4:CMdDwDrf
5:DwnDrft
--
--
103
HTG DEV
MODE
MPrcVal
100
HclDevMod
Heating coil device
mode
Off
--
1:Off
2:CtrlMod
3:FullOpen
--
--
104
HTG COIL
DMD
MCalcVal
101
HclHwDmd
Heating coil hot water
demand
Off
--
1:Off
2:HeatDmd
3:Warm-up
--
--
105
RM UNIT STA4
BAPeriph
eralDevic
e
397
ROpUn 1
Room operator unit 1
Operat.
--
1:Operat.
2:DevStopd
3:DevNAsgn
4:DevMisng
5:CnfngDev
6:Unused
7:CnfError
8:Searchng
--
--
106
OP MODE EFF
MCalcVal
521
PrOpMod
Present operating
mode
Protect
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
107
VAV MODE
MPrcVal
589
VavSuDevMod
Supply air VAV device
mode
Off
--
1:Off
2:CtrlMod
3:MxAiVlFl
4:MnAiVlFl
5:SmCtAFlS
--
--
108
1VAV CHGVR
MPrcVal
590
VavSuChovrCn
d1
Supply air VAV
changeover condition
1
Neither
--
1:Neither
2:Heating
3:Cooling
4:Neutral
--
--