Application

Point Database
91
Siemens Industry, Inc.
A6V11692053
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
112
SU AIR2DMD
MCalcVa
l
596
VavSuAirDmd2
Supply air VAV air
demand 2 f.plant mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:Cooldown
8:RmLTProt
9:CdOvrFPr
10:FreeCool
11:NghtCool
12:Vent
13:EqTmpPro
14:ArVlFlwO
15:SmkCPoPr
16:SmkCNgPr
17:Purge
--
--
BACnet Object Types:
AI, AO, BI, BO, MI, MO Standard BACnet physical inputs and outputs.
APrcVal, BPrcVal, MPrcVal Analog, Binary or Multi-state Process Values are
virtual outputs (not connected to hardware) with priority arrays. They can be
commanded by the application or by external sources.
ACalcVal, BCalcVal, MCalcVal Analog, Binary or Multi-state Calculated Values
are virtual inputs (not connected to hardware) that are only written to by the
application as result of states or calculations.
ACnfVal, BCnfVal, MCnfVal Analog, Binary or Multi-state Configuration Values
are set per job requirements (for example, cooling setpoint for Economy) and
are retained after power cycling.
Additional object types (for example, CmnEvt) are special objects that convey
status information.