Data Sheet for Product

9
Siemens
A6V11259964_en--_b
Smart Infrastructure
Unrestricted
2020-01-16
Wiring connections
Pluggable screw terminals
Copper wire or copper stranded wire with connector sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1 mm
2
(22 to 18 AWG)
Copper stranded wire without connector sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1.5 mm
2
(22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Slotted screws Size 1, tightening torque 0.6 Nm (0.44 lb-ft)
Wiring lengths for signals
KNX PL-Link 80 m (260 ft) with internal bus power or 300
m (990 ft)
with external power supply
MS/TP 1,000 m (3,290 ft)
Signal lines 80 m (260 ft)
For inputs AI 100 kOhm, AI NTC10K, AI NTC100K: 30 m (100 ft) or
80 m (260 ft), if shielded.
KNX/PL-Link Network and Power Wriring.*
Cable configuration 1 or 2 twisted pair
- Pair 1 red/black
- Pair 2 yellow/white
Gauge 20 AWG (solid copper)
Twists per foot 4 Minimum
Capacitance 30 pF/foot or less
Shields 100% foil with drain wire
UL type 300Vrms, CMP (75 °C or higher)
CSA type 300Vrms, FT6 (75 °C or higher)
* Alternative 18 AWG STP CMP (Belden 6320FE 8771000)
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type
Device suited for use with equipment of safety classes I
and II
Degree of protection of housing to IEC EN 60529
Room automation station
IP20
IP30
Climatic ambient conditions
Transport (packaged for transport) as per IEC
EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2K3
Temperature -25...70 °C (-13... 158 °F)
Air humidity 5...95% (non-condensing)
Class 3K5
Temperature -5...50 °C (23... 122 °F)
Air humidity 5...95% (non-condensing)
Mechanical ambient conditions
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2M2
Class 3M2