Differential pressure sensor (inputs P1+, P1-)
Connections (nipple diameter) 5.2 mm
Measuring range 0...500 Pa (02 in WC)
Overload range 0...100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
4.5%
0.2 Pa
12 Bit
Outputs
Analog (output Y10)
Type
Range (over range)
Resolution
Output current
AO 0-10 V 0...10 V (010.5 V) 2 mV Max. 1 mA
AO 0-10 V standard 0...100%
0% = 0 V, 100% = 10 V
(0...10.5 V)
2 mV Max. 1 mA
Switching outputs Triac (outputs Y3...Y6)
Type
High side
The Triac closes the contact to AC 24 V
Switching voltage AC 24 V
Permissible load 500 mA / 12 VA per output
Protection Short-circuit proof
Connections
Interfaces
MS/TP Interface type: RS485
Galvanic isolation: Yes
Baud rates: 9600, 19200, 38400, 57600, 115200
Protocol: BACnet over MS/TP
Short-circuit proof Protection against faulty wiring at max. AC 24 V
USB (2.0) Plug: Type B
Data rate: 12 Mbps
KNX Type: KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Bus power: 50 mA
Short-circuit proof Protection against faulty wiring at max. AC 24 V