Data Sheet for Product
7
Siemens
A6V11259964_en--_b
Smart Infrastructure
Unrestricted
2020-01-16
NOTE:
To calculate the total VA, add the Base Load + the number of Triacs + field supplies+ KNX PL-
Link devices.
This cannot exceed the maximum power consumption. See the
Wiring Guidelines
for more
information.
Inputs
Resistance sensor, analog (inputs X...)
Type
Range (over range)
Resolution
AI 1000 Ohm *) 1 kΩ (0...1.05 kΩ) 1 Ω
AI 2500 Ohm *) 2.5 kΩ (0...2.625 kΩ) 2.5 Ω
AI 10 kOhm *) 10 kΩ (0...10.5 kΩ) 10 Ω
AI 100 kOhm *) 100 kΩ (0...105 kΩ) 100 Ω
Temperature measurement, analog (inputs X...)
Type
Range (over range)
Resolution
AI PT1K 375 (NA) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI PT1K 385 (EU) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI (LG-)Ni1000 *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI Ni1000 DIN *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI T1 (PTC) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.100 K
0.18 °F
AI NTC10K (Type II)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K (@ 25 °C)
0.045 °F (@ 77 °F)
AI NTC100K
-10...70 °C (-15...75 °C)
14...158 °F (5...167 °F)
0.025 K (@ 25 °C)
0.045 °F (@ 77 °F)
*) A fixed value of 1 Ω is calibrated to correct line resistance.
Voltage measurement, analog (inputs X...)
Type
Range (over range)
Resolution
AI 0...10 V 0...10 V (-1...11 V) 2 mV
AI 0...10 V standard 0...100% (-10...110%) 2 mV
Open connection: Negative voltage -1.5 V, 8 μA (line failure detection)
Digital input (inputs X... or D...)
Contact query voltage
Universal input: 18 V
Digital input: 21 V
Contact query current
Universal input: 1.2 mA, 7.4 mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ