Application
Point Database
92
Siemens Industry, Inc.
Application Note
A6V11692053
Smart Infrastructure – Building Products
2019-04-01
14369 ADXR Point Database
The table shows US engineering units and values, and also CA engineering units
and values. CA units are shown in parentheses ( ).
#
Descriptor
Object
Type
Instan
ce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
1
ROOM TEMP 4
AI
39
TR
Room temperature
--
DEG F
(DEG
C)
--
--
--
2
SPLY TEMP 4
AI
110
TSu
Supply air
temperature
--
DEG F
(DEG
C)
--
--
--
3
SU DIFF 1P 3
AI
146
VavSuDiffP1
Supply air VAV
differential pressure 1
--
in H2O
(Pa)
--
--
--
4
SU DIFF 2P 1
AI
147
VavSuDiffP2
Supply air VAV
differential pressure 2
--
in H2O
(Pa)
--
--
--
5
HTG V POS 7
AO
205
HclVlvPos
Heating coil valve
position
--
PCT
--
--
--
6
1DMPR POS 3
AO
289
VavSuPos1
Supply air VAV
position 1
--
PCT
--
--
--
7
2DMPR POS 3
AO
291
VavSuPos2
Supply air VAV
position 2
--
PCT
--
--
--
8
RAD EL POS 2
BO
5
RadElPos 1
Radiator electric
position 1
Off
--
--
On
Off
9
APPLICATION
ACnfVal
4
AppNr
Application number
14369
--
--
--
--
10
CMF CLG
STPT
APrcVal
14
SpCCmf
Cooling setpoint for
comfort
75
(24)
DEG F
(DEG
C)
--
--
--
11
STBY C DELTA
ACnfVal
15
DSpCPcf
Delta cooling setpoint
for pre-comfort
2
(1)
DEG F
(DEG
K)
--
--
--
12
CLG STPT EFF
APrcVal
16
PrSpC
Present cooling
setpoint
--
DEG F
(DEG
C)
--
--
--
13
PROT
CLGSTPT
ACnfVal
17
SpCPrt
Cooling setpoint for
protection
104
(40)
DEG F
(DEG
C)
--
--
--
14
ECO CLG STPT
ACnfVal
18
SpCEco
Cooling setpoint for
economy
85
(30)
DEG F
(DEG
C)
--
--
--
15
STBY C SPEFF
ACalcVal
19
PrSpCPcf
Present cooling
setpoint for pre-
comfort
--
DEG F
(DEG
C)
--
--
--
16
CMF C SP EFF
ACalcVal
20
PrSpCCmf
Present cooling
setpoint for comfort
--
DEG F
(DEG
C)
--
--
--
17
ECO C SP EFF
ACalcVal
21
PrSpCEco
Present cooling
setpoint for economy
--
DEG F
(DEG
C)
--
--
--
18
PROT C SPEFF
ACalcVal
22
PrSpCPrt
Present cooling
setpoint for protection
--
DEG F
(DEG
C)
--
--
--