Application

Room Segment Functions
Device Control Functions HVAC
70
Siemens Industry, Inc.
A6V11692053
Smart Infrastructure Building Products
2019-04-01
temperature detection collection object (RadOvrTDetCol); this collection object is a
common node for any/all RadOvrTDet input object(s).
The RadOvrTDet objects are analyzed using an OR statement. If one or more
objects detect over temperature, the binary result object (RadOvrTDetRs) switches
from 0 to 1, causing the radiator to shut off at equipment protection priority.
Electric power usage: The nominal electric power usage of the electric radiator is
provided for energy monitoring and coordination with other devices. The following
equation calculates the radiator's electric power usage when on (RadElPosVal >
0%):
RadElPwr = RadElPosVal * NomElPwr (zero power is used when radiator is off)
Configuration
Description
Parameter
Default value
Enable overtemperature detector input
▶ Enable input, when a radiator heat over temperature
detector (binary input) is present. When radiator heat
over temperature detector is closed, the radiator l
device mode will turn Off at priority (4:Protection 1).
When radiator heat over temperature detector is open,
the radiator device mode will be released to 15:
Automatic mode 6).
0:No
1:Yes
EnOvrTDetIn
0:No
Nominal electric power
▶ The nominal electric power (kW) for the electric
radiator. The total power for the electric radiator can be
found on manufacturers data sheet.
NomElPwr
0.4 [kW]
Enable downdraft compensation
0:No
1:Yes
EnDndft
0:No
Downdraft characteristics for outside air temperature
X1
▶ Outside air temperature where radiator provides full
(100%) downdraft control.
X1DndftTOa
-5 [°C], 23.0 [°F]
Downdraft characteristics for electric position Y1
▶ The electric radiator position that provides 100%
downdraft control.
Y1DndftElPos
100 [%]
Downdraft characteristics for outside air temperature
X2
▶ Outside air temperature where the electric radiator
begins to provide downdraft control.
X2DndftTOa
10 [°C], 50.0
[°F]
Downdraft characteristics for electric position Y2
▶ The electric radiator position that initializes
downdraft control.
Y2DndftElPos
25 [%]