Assortment / System Description
Fan coil application
Active chilled beam 2-pipe system
17
114 | 275 A6V10866237_en--_b_08
HysTDiffDw
pChw
Hysteresis minimum difference
dew point temperature/chilled
water temperature
TDiffDwpC
hwMin
Minimum difference dew point
temperature/chilled water
temperature
TChwPm Chilled water temperature TDwp Dew point temperature
(calculated)
Figure: Dew point temperature monitoring parameters
Dew point temperature monitoring must be enabled.
Description Name Default value
Enable dew point temperature
0:No
1:Yes
EnTDwp 0:No