Data Sheet for Application

Application Sheet
CEN004
Central function emergency
DXR2..18-101A
DXR2..18-102A
4 / 4
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-01
A6V10662238_en--_d_--_08
Engineering
Digital contact for HVAC
emergency shut down
(D9)
Digital contact for HVAC
Forced smoke extraction
with exhaust air (D10)
Digital contact for HVAC
Forced pressure build up
with supply air (D11)
Resulting HVAC
emergency function in the
rooms
On
Off
Off
Emergency shut down of
all rooms connected to
the group with VAV or fan
coil plants
On
On
Off
Maximum negative
pressure in all rooms
connected to the group
with VAV or fan coil
plants
On
Off
On
Maximum positive
pressure in all rooms
connected to the group
with VAV or fan coil
plants
On
On
On
Maximum purge in all
rooms connected to the
group with VAV or fan
coil plants
WARNING
Desigo TRA is not approved by fire authorities.
Fire can result in death or serious injury.
As a consequence, TRA fire solutions are only used on non-critical
applications with a limited risk to health and risks,
For critical application, an individual permit by the fire authorities on site must
be acquired for a specific project.