Data Sheet for Application
Application Sheet
HP001
Heat pump, variable fan, reversing valve, 2-stage electric heating,
1-stage electric radiator and outside air damper
DXR2..18-102A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662238_en--_c_--_11
• Room temperature control
• Heating and cooling with variable speed heat pump DC 0…10 V
• Modulating control of outside air damper for free cooling when available DC 0…10 V
• 2-stage electric reheater with on/off control on triac
• 1-stage electric radiator with on/off control on triac
• Automatic or manual variable fan speed control DC 0...10 V
• Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
• Presence detector via KNX PL-Link device
Plant diagram
DXR2…
Room automation station
Q8
Variable speed heat pump
B2
Mixed air temperature
R
Room
B3
Supply air temperature sensor
R1
Room operator unit with
B7
Power heat pump
temperature sensor
D2
Presence detector
YOa
Outside air damper
D5
Heat pump fault
YR
Electric reheater, 2-stage
D6
Fan state
YRa
Electric radiator, 1-stage
D7
Condensate level monitor
YRV
Reversing valve heat pump
Q1
Variable speed fan