Data Sheet for Application

Table Of Contents
Application Sheet FPB051/
FPB051_H
Fan powered box with series fan on analog output and staged
electric reheater on triac output
DXR2..18-
102A
2/ 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662238_en--_g_--_03
Description
of functions
Basic functions Options
PID control for supply air and temperature.
3-position damper controlled by triac outputs for VAV
control.
Internal air flow controller controls damper actuator.
The serial fan speed is controlled manual on the room
operator unit or automatic with variable speed.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
2-stage electric reheater.
Parallel fan (supply air), modulating control.
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
Optional system alarms displ
ayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions Variants
Air supply functions to coordinate demand signals for
pressure optimized fan control.
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
FPB application.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
Continuous damper controlled by 0…10 V analog
output for VAV control.
VAV actuator on KNX PL-Link.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices Legend Type of unit Data sheet Product No. Qty.
DXR2… Compact room automation station, BACnet/IP, 24 V,
DIN housing, 2 DI, 4 UI, 8 DO triacs, 4 AO 0…10 V
N9205
N9207
DXR2.E18-102A
DXR2.M18-102A
1
B4 Differential pressure sensor, AC 24 V, DC 0...10 V N1910-1 QBM2030-… 1
B6 Differential pressure sensor, AC 24 V, DC 0...10 V N1910-1 QBM2030-… 1
R1 KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602 QMX3.P34 1
YS Rotary air damper actuator, AC 24 V, 3-position,
5 Nm, 150 s
N4634 GDB131.1E 1