Data Sheet for Application

Application Sheet
VAV082/VAV082_H
Supply and extract VAV with KNX PL-Link VAV controller, heating
and cooling coil and hot water radiator on triac output
DXR2..18-102A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662238_en--_d_--_02
Supply & extract air volume control with compact KNX PL-Link VAV controller
Room temperature control
Air quality control
Heating with LTHW radiator on triac output
Downdraft compensation
Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature, air quality & relative humidity measurement
Plant diagram
Room automation station
R1
Room operator unit with
Extract air temperature sensor
temperature sensor
Supply air temperature sensor
YC
Cooling coil valve
Window contact
YE
Extract air control
Presence detector
YH
Heating coil valve
Room
YR
Radiator valve
YS
Supply air control
Function diagrams
Heating and cooling valve
Air flow
Effective cooling setpoint
VavSuAirFlMinC
Min. volume, cooling
Effective heating setpoint
VavSuAirFlMinH
Min. volume, heating
Room temperature
Y
Output signal
Volume flow rate
YC
Cooling valve
Min. air flow ventilation
YH
Heating valve
Max. volume, cooling
YR
Radiator valve
Max. volume, heating
SpC
0
100
V [%]
TR [°C]SpH
VavSuAirFlMaxC
VavSuAirFlMinC
VavSuAirFlMinH
VavSuAirFlMaxH
VavSuAflMinVnt