User Manual

Application Sheet FPB051
Fan powered box with series fan on analog output and staged
electric reheater on analog output
DXR2..18-
102A
5 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_f_--_03
Default values
Parameter Values/Range Template settings
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
Heating coil Enable overtemperature detector
input
Yes, No Yes
Supply air VAV Supply air VAV max.air vol.flow f.cool 0 … 10’000 m
3
/h 100 m
3
/h
Supply air VAV min.air vol.flow f.cool 0 … 10’000 m
3
/h 50 m
3
/h
Supply air VAV min.air vol.flow f.vent. 0 … 10’000 m
3
/h 0 m
3
/h
Supply air VAV box coefficient 0 … 10’000 m
3
/h/SqrtPa 150 m
3
/h/SqrtPa
Enable monitoring for fan state Yes, No Yes
Fan Maximum fan speed for cooling 0 … 100 % 100 %
Minimum fan speed for cooling 0 … 100 % 50 %
Maximum fan speed for heating 0 … 100 % 100 %
Minimum fan speed for heating 0 … 100 % 50 %
Minimum fan speed for ventilation 0 100 % 50 %
Room operator unit Room unit, display temperature None
Display room temperature
Display room temperature
Room unit, display windows status Yes, No No
Room unit, display heat./cool. status Yes, No Yes
Enable operation: room temp.
setpoint
Yes, No Yes
Room unit, room temp. setpoint
display
Absolute temperature setpoint
Relative setpoint shift
Relative setpoint shift
Enable operation: fan speed setpoint Yes, No Yes
Enable operation: presence button Yes, No No
Enable operation: temporary Comfort Yes, No No
Enable operation: room op. mode Yes, No No
Enable operation: Green Leaf Yes, No Yes