User Manual
Application Sheet FPB051
Fan powered box with series fan on analog output and staged
electric reheater on analog output
DXR2..18-
102A
2 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_f_--_03
Description
of functions
Basic functions Options
∂ PID control for supply air and temperature.
∂ 3-position damper controlled by triac outputs for VAV
control.
∂ Internal air flow controller controls damper actuator.
∂ The serial fan speed is controlled manual on the room
operator unit or automatic with variable speed.
∂ The temperature is measured in the room operator
unit.
∂ The application allows customers to adjust the room
temperature setpoints via the room operator unit.
∂ The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
∂ Change of operating mode via room unit, presence
detector, window contact or central command.
∂ The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
∂ 2-stage electric reheater.
∂ Parallel fan (supply air), modulating control.
∂ Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
∂
Optional system alarms displayed on the management
station notify building operators of possible faults.
∂ Optional trends can be activated for room sensors.
Auxiliary functions Variants
∂ Air supply functions to coordinate demand signals for
pressure optimized fan control.
∂ Green Leaf (RoomOptiControl) function.
∂ Multisegment use of DXR2 automation stations with
FPB application.
∂ The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
∂ Central optimum start control provides best room
comfort at the start of occupancy.
∂ Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
∂ Central override functions for valves.
∂ Seasonal compensation of room temperature
setpoints.
∂ Continuous damper controlled by 0…10 V analog
output for VAV control.
∂ VAV actuator on KNX PL-Link.
∂ PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
∂ The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
∂ Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices Legend Type of unit Data sheet Product No. Qty.
DXR2… Compact room automation station, BACnet/IP, 24 V,
DIN housing, 2 DI, 4 UI, 8 DO triacs, 4 AO 0…10 V
N9205
N9207
DXR2.E18-102A
DXR2.M18-102A
1
B4 Differential pressure sensor, AC 24 V, DC 0...10 V N1910-1 QBM2030-… 1
B6 Differential pressure sensor, AC 24 V, DC 0...10 V N1910-1 QBM2030-… 1
R1 KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602 QMX3.P34 1
YS Rotary air damper actuator, AC 24 V, 3-position,
5 Nm, 150 s
N4634 GDB131.1E 1