Data Sheet for Application

Application Sheet
INT151
Supply and extract VAV with KNX PL-Link VAV controller, heating
and cooling coil, hot water radiator on triac output including
lighting and blinds operation
DXR2..18-102A
2 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-01
A6V10662238_en--_d_--_04
Description
of functions
Basic functions
Options
HVAC
PID control for supply VAV and temperature.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints and rapid ventilation via the
room operator unit including the operation of lighting
and blinds.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
VAV actuator on KNX PL-Link.
HVAC
Extract VAV actuator on KNX PL-Link.
PID control LTHW radiator heating.
Heating and cooling coils with 3 position valves
controlled by triac outputs.
Downdraft compensation.
Outside temperature (for downdraft compensation)
distributed over BACnet.
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector
or window contact.
Optional system alarms displayed on the
management station notify building operators of
possible faults.
Optional trends can be activated for room sensors.
Lighting
The application allows room users to control lighting
via a standard function switching and/or
The application allows customers to control lighting
operation via room unit.
Lighting
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective electronic control gear
or lamps).
Optional trends can be activated for room lighting.
Blinds
The application allows room users to operate the
blinds via the following commands:
o Move up/down
o Step up/down
The reference model applied ensures exact
positioning of the shading products.
The application allows customers to control shading
operation via room unit.
Blinds
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective actuator).
Reliable, central override of local operation only for
emergencies, service, and cleaning.
Central weather protection function preventing
damages to shading products due to high winds or
frost.
Optional trends can be activated for room blinds.
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
VAV application.
Standard hot water supply chain control.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
KNX PL-Link switches for lighting and blinds
operation.
Presence can be detected by KNX PL-Link sensor
or binary sensor.
Lighting
The application allows for control via centralized
commands (e.g. scheduler program).
The application function supports runtime totalization
for each lighting group for maintenance and service
purposes (burn in/operation h/EOL end of life cycle).
Blinds
The application allows for control via centralized
commands (e.g. scheduler program or weather
station).