Data Sheet for Application
Application Sheet
INT151
Supply and extract VAV with KNX PL-Link VAV controller, heating
and cooling coil, hot water radiator on triac output including
lighting and blinds operation
DXR2..18-102A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-01
A6V10662238_en--_d_--_04
• Supply & extract air volume control with compact KNX PL-Link VAV controller
• Room temperature control
• Heating with LTHW radiator on triac output
• Downdraft compensation
• Including the control of 4 lighting zones & 2 blinds
• Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature measurement & lighting and blinds operation
Plant diagram
DXR2…
Room automation station
R
Room
B1
Extract air temperature sensor
R1
Room operator unit with
B3
Supply air temperature sensor
temperature sensor
D1
Window contact
YC
Cooling coil valve
D2
Presence detector
YE
Extract air control
Q2, Q3,
4 lighting zones
YH
Heating coil valve
Q4, Q5
YR
Radiator valve
Q6, Q7
2 blinds motors
YS
Supply air control
Function diagrams
Heating and cooling valve
Airflow
SpC
Effective cooling setpoint
VavSuAirFlMinC
Min. volume, cooling
SpH
Effective heating setpoint
VavSuAirFlMinH
Min. volume, heating
TR
Room temperature
Y
Output signal
V
Volume flow rate
YC
Cooling valve
VavSuAflMinVent
Min. air flow ventilation
YH
Heating valve
VavSuAirFlMaxC
Max. volume, cooling
YR
Radiator valve
VavSuAirFlMaxH
Max. volume, heating
SpC
0
100
V [%]
TR [°C]SpH
VavSuAirFlMaxC
VavSuAirFlMinC
VavSuAirFlMinH
VavSuAirFlMaxH
VavSuAflMinVnt