Data Sheet for Application

Application Sheet
INT151
Supply and extract VAV with KNX PL-Link VAV controller, heating
and cooling coil, hot water radiator on triac output including
lighting and blinds operation
DXR2..18-102A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-01
A6V10662238_en--_d_--_04
Supply & extract air volume control with compact KNX PL-Link VAV controller
Room temperature control
Heating with LTHW radiator on triac output
Downdraft compensation
Including the control of 4 lighting zones & 2 blinds
Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature measurement & lighting and blinds operation
Plant diagram
Room automation station
R
Room
Extract air temperature sensor
R1
Room operator unit with
Supply air temperature sensor
temperature sensor
Window contact
YC
Cooling coil valve
Presence detector
YE
Extract air control
4 lighting zones
YH
Heating coil valve
YR
Radiator valve
2 blinds motors
YS
Supply air control
Function diagrams
Heating and cooling valve
Airflow
SpC
Effective cooling setpoint
VavSuAirFlMinC
Min. volume, cooling
SpH
Effective heating setpoint
VavSuAirFlMinH
Min. volume, heating
TR
Room temperature
Y
Output signal
V
Volume flow rate
YC
Cooling valve
VavSuAflMinVent
Min. air flow ventilation
YH
Heating valve
VavSuAirFlMaxC
Max. volume, cooling
YR
Radiator valve
VavSuAirFlMaxH
Max. volume, heating
SpC
0
100
V [%]
TR [°C]SpH
VavSuAirFlMaxC
VavSuAirFlMinC
VavSuAirFlMinH
VavSuAirFlMaxH
VavSuAflMinVnt