Data Sheet for Product

6
Siemens Industry, Inc.
A
Smart Infrastructure
Outputs
Analog Outputs
0 to 10V Max. 1 mA
Digital Outputs
Type (Switching outputs triacs) High side
The Triac closes the contact to AC 24V
Switching voltage AC 24V
Permissible load 250 mA/6 VA per output (cos phi 0.35)
(500 mA/12 VA per output with PWM*)
Protection Short-circuit proof
DC 24V output for field devices (1: V+)
Output voltage DC 24V
Permissible load 100 mA/2.4 W
Protection against overload Short-circuit proof
Connections
Interfaces
Ethernet Plugs: 2 x RJ45, screened
Interface type: 10Base-T/100BASE-TX, IEEE 802.3 compatible
Bitrates: 10/100 Mbps, autosensing
Protocol: BACnet over UDP/IP
USB (2.0) Plug: Type B
Data rate: 12 Mbps
KNX Type: KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 Kbps
Bus power: 50 mA
Short-circuit proof Protection against faulty wiring at max. AC 24V
Wiring connections
Pluggable screw terminals Copper wire or copper strands with ferrules
1 x 0.6 mm dia. to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.5 mm dia. to 1 mm
2
(24 to 18 AWG)
Copper strands without ferrules
1 x 0.6 mm dia. to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.5 mm dia. to 1.5 mm
2
(24 to 16 AWG)
Slotted screws Small 1/8” blade, tightening torque 0.6 Nm (0.44 lb-ft)
Wiring lengths for signals KNX PL-Link 80 m (260 ft) with internal bus power or 300 m (990
ft) with external power supply
Ethernet 100 m (330 ft)
Signal lines 80 m (260 ft)
For inputs AI 100 KΩ, AI NTC10K, AI NTC100K:
30 m (100 ft) or 80 m (260 ft), if shielded.