Application Sheet CBA001
Active chilled beam with KNX PL-Link VAV controller, cooling coil
and hot water radiator on triac output
DXR2..18-
101A
DXR2..18-
102A
4 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_b_--_10
Application
configuration
Equipment Values/Range Template settings
KNX PL-Link devices Room operator unit device 1 QMX3.P02, QMX3.P34, QMX3.P36, QMX3.P37,
QMX3.P74
QMX3.P74
Supply air VAV device GDB181.1E/KN
GLB181.1E/KN
GDB181.1E/KN
Optional
configuration
Equipment Values/Range Template settings
On-board output Cooling coil valve position Water; Y3, Y4; 3-position
Water; Y3; Pulse width modulation thermal
Water; Y3; Pulse width modulation spring return
Water; Y20; 0...10 V
Chilled beam active; Y3, Y4; 3-position
Chilled beam active; Y3; Pulse width modulation
thermal
Chilled beam active; Y3; Pulse width mod.spring
return
Chilled beam active; Y20; 0...10 V
Chilled beam active;
Y3, Y4; 3-position
Radiator valve position Water; Y3, Y4; 3-position
Water; Y7, Y8; 3-position
Water; Y3; Pulse width modulation thermal
Water; Y7; Pulse width modulation thermal
Water; Y3; Pulse width modulation spring return
Water; Y7; Pulse width modulation spring return
Water; Y20; 0...10 V
Water; Y40; 0...10 V
Electric 1-stage; Y3; Normally open
Electric 1-stage; Y7; Normally open
Electric modulating; Y3; Pulse width modulation
constant period
Electric modulating; Y7; Pulse width modulation
constant period
Electric modulating; Y20; 0...10 V
Electric modulating; Y40; 0...10 V
Water; Y7, Y8; 3-position
KNX PL-Link devices Extract air VAV device GDB181.1E/KN
GLB181.1E/KN
GDB181.1E/KN
On-board input Room temperature (B1) X1; LG-Ni1000
Supply air temperature (B3) X2; LG-Ni1000
Presence detector 2 (D2
a
)
D2; Normally open
Window contact (D1) D1; Normally closed
KNX PL-Link devices Sensor device 1…4 (D2) UP 258D12